Copper Tape Screen Steel Wire Armoured Cable SWA 35kV High Voltage
| Screen: | Copper Tape | Armour: | Steel Wire |
| Voltage: | High Voltage | Insulation: | XLPE |
| Sheath: | HDPE | Price: | Factory Price |
| High Light: | High Voltage Steel Wire Armoured Cable,35kV High Voltage Armoured Cable,Copper Tape Screen Armoured Cable |
||
Copper Tape Screen Steel Wire Armoured Electrical Cable SWA 35kV High Voltage
Application
- Power Transmission Networks
- Renewable Energy Systems
- Industrial Facilities
- Urban Grid Upgrades
- Special Environments
Construction
- Conductor Class 2 copper conductor or Aluminium , compacted or segment strand Milliken
- Conductor Screen: Extruded semi-conductive XLPE (Cross-Linked Polyethylene)
- Insulation XLPE (Cross-Linked Polyethylene)
- Insulation Screen: Extruded Semi-conductive XLPE (Cross-Linked Polyethylene)
- Separator: Water swellable semi-conductive tap
- Screen: Copper wire screen, with a counter helix of copper tape
- Sheath: HDPE (High Density Polyethylene)
Technical data
- Voltage Rating (Uo/U)(Um): 64/110kV (123kV)
- Highest Network Voltage: 123kV
- Operating Temperature: -30°C to +90°C
- Short Circuit Temperature: +250°C
- Overload Temperature: +130°C (100h per y
Specification
|
Parameter category |
Parameter item |
parameter values |
|
configuration parameter |
electric conductor |
Material: copper core (cross-section range: 630~1600mm²) |
|
External diameter of conductor |
30.0~56.5mm (The larger the section, the increasing the outer diameter) |
|
|
insulating course |
Material: Cross-linked polyethylene (XLPE), thickness of 16.5±0.5mm |
|
|
Conductor shielding layer |
Thickness of 1.2mm (semi-conductive material) |
|
|
insulation screen |
Thickness of 1.0mm (semi-conductive material) |
|
|
metallic sheath |
Wrinkle aluminum sheath (2.0±0.2mm) (double galvanized steel strip, 0.5~0.8mm) |
|
|
oversheath |
Material: flame retardant polyvinyl chloride (PVC) or polyethylene (PE), thickness of 4.5±0.2mm |
|
|
Electrical parameters |
20℃ conductor DC resistance |
0.0754~0.009 Ω / km (the larger the section, the lower the resistance) |
|
90℃ conductor AC resistance |
0.097~0.0142Ω/km |
|
|
capacity value |
134-282 p F/m (increased with increasing cross-section) |
|
|
Power frequency pressure test |
64 / 110kV (factory test) |
|
|
Local discharge performance |
At 5pC(1.5U₀ under-voltage) |
|
|
Mechanical and laying parameters |
minimum bending radius |
12 x cable outer diameter (armor layer requirement) |
|
Allow working temperature |
Long-term: 90℃, short circuit (within 5 seconds): 250℃ |
|
|
Laying ambient temperature |
≥0℃ |
|
|
Vehicle flow reference |
Flow rate in single return air |
Section 630mm²: 1010A; section 1600mm²: 1690A (ambient temperature 40℃, soil thermal resistance 1.0m · ℃ / W) |
|
Load flow rate of directly buried laying |
Section 630mm²: about 800A; section 1600mm²: about 1300A (buried depth 1m, ground temperature 35℃) |