CU/PVC/PVC Ongewapend Besturingskabel 0.6/1kV Koperen Geleider PVC Geïsoleerd Mantel Multi-core IEC 60502-1
| Type: | Unshielded Controlekabel | Voltage Rating: | 0.6/1kV |
| Number of Cores: | 2-61 kernen | Conductor: | Koper, klasse 1 / klasse 2 / klasse 5 (IEC 60228) |
| Insulation: | PVC | Outer Sheath: | PVC ST2 |
| Max Operating Temperature: | 70 graden C | Standards: | IEC 60502-1 / IEC 60228 |
| Installation: | Binnen, kabelgoten, leidingen, schakelkasten | Cross Reference: | VV / KVV-equivalent |
| High Light: | 0.6/1kV Nominale Besturingskabel,Koper PVC PVC Constructie,IEC 60502-1 Conform Kabel |
||
CU/PVC/PVC-besturingskabel 0,6/1kV
De CU/PVC/PVC 0,6/1kV besturingskabel vervaardigd door Zhongdong Cable is ontworpen voor vaste besturings-, bewakings- en hulpelektrische toepassingen in industriële, commerciële,en infrastructuurprojecten.
De kabel bestaat uit koperen geleiders, PVC-isolatie en PVC-buitenste behuizing, die betrouwbare elektrische prestaties, goede flexibiliteit en economische installatie biedt.De eenvoudige en duurzame structuur maakt het geschikt voor algemene besturingscircuits waarbij geen elektromagnetisch afscherming en aanvullende mechanische bescherming nodig zijn.
CU/PVC/PVC-besturingskabels worden veel gebruikt in automatiseringssystemen, elektrische panelen, machineriebesturingscircuits en laagspanningsbesturingstoepassingen waarvoor stabiele en kosteneffectieve kabeloplossingen nodig zijn.
Snelle specificaties
- Type:Onbeschermde besturingskabel
- Standaardspanning:0.6/1kV
- Kernen:Multi-kern beschikbaar (2-61 kernen)
- Leider:Klasse 1 / Klasse 2 / Klasse 5 koper (IEC 60228)
- Isolatie:PVC (polyvinylchloride)
- Buitenmantel:PVC ST2
- Configuratie:met een vermogen van niet meer dan 50 W
- Installatie:Inrichting, kabelbakken, leidingen, bedieningskasten en vaste installaties
- Normen:IEC 60502-1 / IEC 60228
- Kruisverwijzingen:VV/KVV-equivalent (afhankelijk van de toepassing)
Bouw
- Leider:Plain gegalveerde koperen geleider, vast of met strengen volgens de grootte van de geleider.
- Isolatie:PVC-isolatie zorgt voor elektrische isolatie en betrouwbare werking bij nominale spanning.
- Montage:Geïsoleerde kernen worden samen met geschikte vulstoffen (voor meerkernkabels) gelegd om een compacte kabelstructuur te vormen.
- Buitenmantel:PVC-slijm biedt mechanische bescherming en weerstand tegen vocht, slijtage en buitenomstandigheden.
Toepassingen
De CU/PVC/PVC 0,6/1kV besturingskabel is ontworpen voor algemene besturing en laagspanningshulpscircuits waar geen afscherming en pantsering nodig zijn.
- industriële besturingspanelen
- Elektrische kasten en schakelborden
- Bedrading van automatiseringsapparatuur
- Stelsels voor het bedienen van machines
- Gebouwcontroleinrichtingen
- motorbesturingscircuits
- HVAC- en gebouwbeheersystemen
- Fabrieksproductie
- Hulpverbindingen voor stroomvoorziening en besturing
- Vaste elektrische installaties voor binnenshuis
Normen
IEC 60502-1, IEC 60228
Technische gegevens (IEC 60502-1)
| Nummer van de kern x sectie (nr. x mm2) | Type geleider | Isolatiedikte (mm) | Dikte van de omhulsel (mm) | Algemene diameter (mm) | Ongeveer Gewicht (kg/km) | Max. gelijkstroomweerstand bij 20 °C (ohm/km) |
| 2x0.5 | 2 | 0.6 | 1.8 | 8.1 | 74 | 36 |
| 2x1 | 2 | 0.6 | 1.8 | 8.9 | 98 | 18.1 |
| 2x1.5 | 2 | 0.8 | 1.8 | 10.3 | 131 | 12.1 |
| 2x2.5 | 2 | 0.8 | 1.8 | 11.1 | 157 | 7.41 |
| 2x6 | 2 | 1 | 1.8 | 14.1 | 265 | 3.08 |
| 4x0.5 | 2 | 0.6 | 1.8 | 9 | 97 | 36 |
| 4x1 | 2 | 0.6 | 1.8 | 9.9 | 138 | 18.1 |
| 4x1.5 | 2 | 0.8 | 1.8 | 11.6 | 191 | 12.1 |
| 4x2.5 | 2 | 0.8 | 1.8 | 12.6 | 240 | 7.41 |
| 4x6 | 2 | 1 | 1.8 | 16.2 | 445 | 3.08 |
| 7x0.5 | 2 | 0.6 | 1.8 | 10.2 | 131 | 36 |
| 7x1 | 2 | 0.6 | 1.8 | 11.4 | 182 | 18.1 |
| 7x1.5 | 2 | 0.8 | 1.8 | 13.5 | 259 | 12.1 |
| 7x2.5 | 2 | 0.8 | 1.8 | 14.7 | 341 | 7.41 |
| 7x6 | 2 | 1 | 1.8 | 19.2 | 657 | 3.08 |
| 10x0.5 | 2 | 0.6 | 1.8 | 12.3 | 179 | 36 |
| 10x1 | 2 | 0.6 | 1.8 | 13.9 | 252 | 18.1 |
| 10x1.5 | 2 | 0.8 | 1.8 | 16.7 | 360 | 12.1 |
| 10x2.5 | 2 | 0.8 | 1.8 | 18.3 | 478 | 7.41 |
| 10x6 | 2 | 1 | 1.8 | 24.3 | 932 | 3.08 |
| 12x0.5 | 2 | 0.6 | 1.8 | 12.6 | 195 | 36 |
| 12x1 | 2 | 0.6 | 1.8 | 14.3 | 280 | 18.1 |
| 12x1.5 | 2 | 0.8 | 1.8 | 17.2 | 406 | 12.1 |
| 12x2.5 | 2 | 0.8 | 1.8 | 18.9 | 543 | 7.41 |
| 12x6 | 2 | 1 | 1.8 | 25.1 | 1072 | 3.08 |
| 19x0.5 | 2 | 0.6 | 1.8 | 14.4 | 271 | 36 |
| 19x1 | 2 | 0.6 | 1.8 | 16.4 | 400 | 18.1 |
| 19x1.5 | 2 | 0.8 | 1.8 | 19.9 | 592 | 12.1 |
| 19x2.5 | 2 | 0.8 | 1.8 | 22 | 802 | 7.41 |
| 19x6 | 2 | 1 | 1.9 | 29.9 | 1643 | 3.08 |
| 24 uur per dag.5 | 2 | 0.6 | 1.8 | 16.5 | 338 | 36 |
| 24x1 | 2 | 0.6 | 1.8 | 18.8 | 500 | 18.1 |
| 24 uur per dag.5 | 2 | 0.8 | 1.8 | 23 | 739 | 12.1 |
| 24 uur per dag.5 | 2 | 0.8 | 1.8 | 25.6 | 1006 | 7.41 |
| 24x6 | 2 | 1 | 2 | 35.1 | 2084 | 3.08 |
| 37x0.5 | 2 | 0.6 | 1.8 | 18.6 | 464 | 36 |
| 37x1 | 2 | 0.6 | 1.8 | 21.3 | 707 | 18.1 |
| 37x1.5 | 2 | 0.8 | 1.8 | 26.2 | 1064 | 12.1 |
| 37x2.5 | 2 | 0.8 | 1.9 | 29.7 | 1485 | 7.41 |
| 37x6 | 2 | 1 | 2.2 | 40.6 | 3108 | 3.08 |
| 61x0.5 | 2 | 0.6 | 1.8 | 22.8 | 711 | 36 |
| 61x1 | 2 | 0.6 | 1.8 | 26.3 | 1102 | 18.1 |
| 61x1.5 | 2 | 0.8 | 2 | 33.3 | 1714 | 12.1 |
| 61x2.5 | 2 | 0.8 | 2.1 | 37.3 | 2386 | 7.41 |
| 61x6 | 2 | 1 | 2.6 | 51.6 | 5065 | 3.08 |
Hierboven weergegeven representatieve technische gegevens: op aanvraag is een volledige gegevenstabel beschikbaar voor alle kerngetallen (2-61 kernen) en doorsneden (0,5-10 mm2).
Veelgestelde vragen
V1: Wat is een CU/PVC/PVC-besturingskabel?
A: Een CU/PVC/PVC-besturingskabel is een laagspanningsbesturingskabel die bestaat uit koperen geleiders, PVC-isolatie en PVC-buitenste omhulsel.met een vermogen van niet meer dan 10 W.
V2: Wat is het verschil tussen CU/PVC/PVC en CU/PVC/CTS/PVC besturingskabel?
A: CU/PVC/PVC is een niet-beschermde kabel voor standaardbesturingstoepassingen, terwijl CU/PVC/CTS/PVC een koperen bandscherm bevat om de bescherming tegen elektromagnetische interferentie te verbeteren.
V3: Waar wordt CU/PVC/PVC-besturingskabel vaak gebruikt?
A: Het wordt vaak gebruikt in bedieningskasten, industriële apparatuur, automatiseringssystemen, elektrische installaties van gebouwen en algemene laagspanningsbesturingscircuits.
V4: Is een CU/PVC/PVC-besturingskabel geschikt voor binneninstallatie?
A: Ja. Het wordt veel gebruikt voor vaste installaties in huis, zoals besturingspanelen, elektrische kastjes en bedradingssystemen voor apparatuur.
V5: Kan deze kabel worden gebruikt voor ondersteunende stroomcircuits?
A: Ja. Afhankelijk van de grootte van de geleider en de projectvereisten kunnen CU/PVC/PVC-kabels worden gebruikt voor hulptoepassingen op het gebied van stroomvoorziening en besturing.
V6: Welke geleideropties zijn er voor deze kabel?
A: De kabel kan worden geleverd met vaste koperen geleiders (klasse 1), strenge koperen geleiders (klasse 2) of flexibele koperen geleiders (klasse 5) volgens IEC 60228.
V7: Wat is de maximale werktemperatuur van CU/PVC/PVC-kabels?
A: De PVC-isolatie maakt een continue werking van de geleider mogelijk tot 70°C onder normale bedrijfsomstandigheden.
V8: Kan CU/PVC/PVC-besturingskabel voor speciale toepassingen worden aangepast?
A: Ja. Vlamvertragende, rookvrije halogeen (LSZH) en andere op maat gemaakte kabelconstructies kunnen worden geleverd volgens de projectvereisten.