4 Core SWA Armoured Electrical Cable 0.6/1kV IEC 60502 Steel Wire Armor for Underground Power Distribution
| Conductor Material: | مس | Core Number: | 4 هسته |
| Voltage Rating: | 0.6/1kV | Insulation Material: | XLPE |
| Armor Type: | SWA (زره سیم فولادی) | Standard: | IEC 60502 |
| Conductor Cross-section: | 1.5 میلی متر مربع - 630 میلی متر مربع | Sheath Material: | پی وی سی |
| Operating Temperature: | ۹۰ درجه سانتیگراد | ||
| High Light: | SWA Steel Wire Armored Cable,IEC 60502 Armoured Power Cable,0.6/1kV Underground Distribution Cable |
||
4 Core SWA Armoured Electrical Cable 0.6/1kV IEC 60502 Steel Wire Armor for Underground Power Distribution
Product Introduction
The 4 Core SWA (Steel Wire Armor) Armoured Electrical Cable rated 0.6/1kV is engineered in strict accordance with IEC 60502 standards. Featuring copper conductors, XLPE (Cross-Linked Polyethylene) insulation, and a galvanized steel wire armor layer, this cable delivers exceptional mechanical protection and electrical performance for underground power distribution, industrial power transmission, and infrastructure EPC projects. The 4-core configuration (3-phase + neutral) makes it the standard choice for balanced 3-phase power delivery in harsh installation environments.
Designed for direct burial, cable trench, and outdoor installation, this SWA cable provides long-term reliability under demanding conditions including moisture, mechanical stress, and chemical exposure. Its XLPE insulation allows a maximum operating temperature of 90 °C, ensuring stable performance in continuous-duty applications.
Application Scenarios
|
Industry |
Application |
Recommended Product |
|---|---|---|
|
Power Utility |
Substation feeder, underground distribution network |
SWA Armoured Cable 0.6/1kV |
|
Oil & Gas |
Refinery power supply, chemical plant wiring |
SWA Armoured Cable 0.6/1kV |
|
Mining |
Mine site power distribution, conveyor motor supply |
SWA Armoured Cable 0.6/1kV |
|
Infrastructure |
Metro, tunnel, bridge, and highway EPC projects |
SWA Armoured Cable 0.6/1kV |
|
Industrial |
Factory main feeder, heavy machinery power supply |
SWA Armoured Cable 0.6/1kV |
|
Commercial |
Shopping mall, hospital, data center power backbone |
SWA Armoured Cable 0.6/1kV |
Mining Industry Requirements
Mining environments demand cables with abrasion resistance, flame retardancy, mechanical protection, and moisture resistance. Our SWA armoured cable meets all these criteria with its robust steel wire armor and durable PVC outer sheath.
Oil & Gas Industry Requirements
Oilfield and refinery projects require chemical resistance, UV resistance, and reliable high temperature performance. The XLPE insulation and SWA construction in this cable provide the durability needed for petrochemical environments.
Technical Specifications
|
Parameter |
Specification |
|---|---|
|
Voltage Rating |
0.6/1kV |
|
Core Number |
4 Core |
|
Conductor Material |
Copper |
|
Conductor Cross-section |
1.5 mm² - 630 mm² |
|
Insulation Material |
XLPE (Cross-Linked Polyethylene) |
|
Armor Type |
SWA (Galvanized Steel Wire Armor) |
|
Outer Sheath |
PVC (Polyvinyl Chloride) |
|
Standard |
IEC 60502 |
|
Max Operating Temperature |
90 °C |
|
Short-circuit Temperature |
250 °C (max 5 seconds) |
|
Minimum Bending Radius |
15 x cable diameter |
|
Installation Method |
Direct burial, cable trench, duct, outdoor |
4-Core Conductor Technical Data (Copper, XLPE Insulated, 0.6/1kV)
|
Nominal Cross-section (mm²) |
Conductor Diameter (mm) |
Insulation Thickness (mm) |
Armor Wire Diameter (mm) |
Sheath Thickness (mm) |
Overall Diameter Approx. (mm) |
Approx. Weight (kg/km) |
Current Rating in Air (A) |
Current Rating Buried (A) |
Voltage Drop (mV/A/m) |
|---|---|---|---|---|---|---|---|---|---|
|
4 x 1.5 |
1.38 |
0.7 |
0.9 |
1.4 |
13.8 |
345 |
21 |
25 |
31 |
|
4 x 2.5 |
1.78 |
0.7 |
0.9 |
1.4 |
15.0 |
425 |
28 |
33 |
19 |
|
4 x 4 |
2.25 |
0.7 |
1.25 |
1.5 |
17.0 |
575 |
36 |
42 |
12 |
|
4 x 6 |
2.76 |
0.7 |
1.25 |
1.5 |
18.5 |
720 |
46 |
53 |
7.9 |
|
4 x 10 |
3.57 |
0.7 |
1.25 |
1.6 |
21.0 |
1020 |
62 |
70 |
4.7 |
|
4 x 16 |
4.51 |
0.7 |
1.6 |
1.7 |
24.0 |
1450 |
82 |
91 |
2.9 |
|
4 x 25 |
5.64 |
0.9 |
1.6 |
1.8 |
28.0 |
2100 |
108 |
117 |
1.85 |
|
4 x 35 |
6.68 |
0.9 |
1.6 |
1.9 |
31.5 |
2750 |
132 |
140 |
1.35 |
|
4 x 50 |
8.00 |
1.0 |
1.6 |
2.0 |
36.0 |
3700 |
160 |
167 |
0.98 |
|
4 x 70 |
9.50 |
1.1 |
2.0 |
2.2 |
40.5 |
4950 |
200 |
205 |
0.67 |
|
4 x 95 |
11.0 |
1.1 |
2.0 |
2.3 |
45.5 |
6450 |
244 |
245 |
0.49 |
|
4 x 120 |
12.4 |
1.2 |
2.5 |
2.5 |
50.5 |
8100 |
282 |
278 |
0.39 |
|
4 x 150 |
13.8 |
1.4 |
2.5 |
2.7 |
56.0 |
9900 |
325 |
314 |
0.31 |
|
4 x 185 |
15.3 |
1.6 |
2.5 |
2.9 |
61.5 |
11950 |
372 |
354 |
0.25 |
|
4 x 240 |
17.5 |
1.7 |
3.15 |
3.1 |
69.0 |
15350 |
440 |
410 |
0.195 |
|
4 x 300 |
19.6 |
1.8 |
3.15 |
3.3 |
76.0 |
18900 |
506 |
463 |
0.158 |
|
4 x 400 |
22.6 |
2.0 |
3.15 |
3.5 |
86.0 |
24400 |
584 |
525 |
0.124 |
Engineering Advantages
-
Superior Mechanical Protection: Galvanized SWA layer shields the cable core from external impact, crushing, and rodent damage, making it suitable for direct burial and harsh industrial environments.
-
High Current Carrying Capacity: Copper conductors with XLPE insulation enable higher ampacity compared to PVC-insulated cables of the same cross-section, reducing energy loss over long cable runs.
-
Flame Retardant Performance: PVC outer sheath offers inherent flame retardancy, limiting fire propagation in the event of an electrical fault.
-
Moisture & Chemical Resistance: The continuous steel wire armor combined with the PVC sheath provides an effective barrier against water ingress and chemical exposure in underground installations.
-
UV Resistance: The outer PVC sheath is formulated to withstand prolonged outdoor exposure without degradation, suitable for above-ground installation sections.
-
Suitable for EPC Projects: Compliant with IEC 60502 international standards, accepted by engineering procurement and construction contractors worldwide.
Standards & Certifications
-
CE - European conformity marking
-
EAC - Eurasian Conformity mark (CU TR 004/2011), required for Russia, Belarus, Kazakhstan, Armenia, and Kyrgyzstan markets
-
ISO 9001:2015 - Quality management system certification
-
3C (CCC) - China Compulsory Certification for electrical products
-
IEC 60502 - Power cables with extruded insulation and their accessories for rated voltages from 1kV up to 30kV
-
Third-party testing reports available upon request (routine test, sample test, type test)
- Power cables with extruded insulation and their accessories for rated voltages from 1kV up to 30kV
-
ISO 9001:2015 - Quality management system certification
-
CE - European conformity marking
-
Third-party testing reports available upon request (routine test, sample test, type test)
FAQ
Q1: Is SWA armoured cable suitable for underground direct burial?
A: Yes, SWA armoured cable is specifically designed for underground direct burial. The galvanized steel wire armor provides excellent mechanical protection against soil pressure, rocks, and potential rodent damage. No additional conduit is required in most installations per IEC 60502 guidelines.
Q2: What is the difference between XLPE and PVC cable insulation?
A: XLPE (Cross-Linked Polyethylene) offers a higher operating temperature (90°C vs 70°C for PVC), greater current carrying capacity for the same conductor size, lower dielectric losses, and better moisture resistance. It is the preferred insulation material for modern power distribution cables.
Q3: What standards does this cable comply with?
A: This cable is manufactured to IEC 60502, the international standard for power cables with extruded insulation. We can also manufacture to BS 5467, ASTM, or other national standards upon request.
Q4: How to select the correct cable size for an industrial project?
A: Cable sizing depends on load current, voltage drop, installation method, ambient temperature, and grouping factors. We recommend consulting our engineering team with your project specifications (load in kW/A, cable length, installation environment) to determine the optimal conductor cross-section.
Q5: What is the typical service life of XLPE insulated SWA cable?
A: When installed correctly and operated within rated parameters, XLPE insulated SWA cables have an expected service life of 30+ years. Key factors include proper burial depth, avoiding mechanical damage during installation, and adherence to rated current and temperature limits.