| 전압: | 0.6/1kv | 전도체 물질: | 알류미늄 |
|---|---|---|---|
| 격리: | XLPE | 외부 칼집: | PVC |
| 코어 수: | 단일 코어 | 화재 시 행동: | IEC 60332-1 |
| 애플리케이션: | 저전압 분배 | ||
| 강조하다: | YJLV aluminum power cable,0.6/1kV low voltage cable,single core XLPE PVC cable |
||
Product Overview
The NA2XY – YJLV (AL/XLPE/PVC) Single Core 0.6/1kV is a high-performance low voltage power cable designed for reliable and cost-effective electricity distribution in 0.6/1kV systems. This cable features an aluminum conductor, XLPE (cross-linked polyethylene) insulation, and a PVC outer sheath.
Offering an excellent balance between cost efficiency and electrical performance, the NA2XY/YJLV cable is widely used as a lightweight, affordable alternative to copper cables in fixed installations. The XLPE insulation provides superior thermal resistance (90°C continuous operation), while the PVC sheath delivers reliable mechanical and environmental protection .
European designation: NA2XY
Chinese designation: YJLV
Voltage rating: 0.6/1kV (U₀/U)
Number of cores: Single core
Conductor material: Aluminum (Class 1 or Class 2)
Insulation: XLPE (Cross-linked Polyethylene)
Sheath: PVC (Polyvinyl Chloride)
Standards: IEC 60502-1, GB/T 12706, IEC 60228
Key Features
| Feature | Benefit |
|---|---|
| Aluminum conductor | 50% lighter than copper – easier handling, lower transportation and installation costs |
| XLPE insulation | High thermal rating (90°C continuous, 250°C short circuit) – superior to PVC |
| PVC outer sheath | Good mechanical protection, moisture resistance, and UV stability |
| 0.6/1kV rating | Suitable for most low voltage power distribution applications |
| Single core design | Flexible installation, easy termination |
| Cost-effective | 40-60% lower material cost compared to copper equivalents |
| IEC compliant | Manufactured to IEC 60502-1 and GB/T 12706 standards |
| Wide size range | Available from 1.5mm² up to 800mm² |
Applications
The NA2XY – YJLV (AL/XLPE/PVC) Single Core 0.6/1kV is widely used in the following applications:
1. Low Voltage Power Distribution
2. Building Electrical Systems
3. Industrial Installations
4. Outdoor and Underground
5. Renewable Energy Projects
6. Infrastructure Projects
Construction Details
| Layer | Material | Specification | Function |
|---|---|---|---|
| Conductor | Aluminum | Class 1 (solid) or Class 2 (stranded) per IEC 60228 | High conductivity, lightweight |
| Conductor Screen | Semi-conductive XLPE | For screened versions (optional) | Even electrical stress distribution |
| Insulation | XLPE (Cross-linked Polyethylene) | 90°C rated | High dielectric strength, thermal stability |
| Insulation Screen | Semi-conductive XLPE | For screened versions (optional) | Stress control |
| Filler | Polypropylene (for multi-core) | Maintains circular shape | Core stability |
| Inner Sheath | Optional | Bedding for armoured versions | Protection |
| Outer Sheath | PVC (Type ST2) | Black or custom color, UV stabilized | Mechanical and environmental protection |
*Note: This is an unarmoured cable. For applications requiring mechanical protection (direct burial or rodent-prone areas), armoured versions (YJLV32 / NA2XY with SWA) are recommended .*
Technical Specifications
| Parameter | Value |
|---|---|
| Rated Voltage (U₀/U) | 0.6/1kV |
| Maximum Operating Voltage | 1.2kV |
| Standard | IEC 60502-1, GB/T 12706 |
| Conductor Material | Aluminum (99.5% purity) |
| Conductor Types | Class 1 (solid) or Class 2 (stranded) per IEC 60228 |
| Conductor Sizes Available | 1.5mm², 2.5mm², 4mm², 6mm², 10mm², 16mm², 25mm², 35mm², 50mm², 70mm², 95mm², 120mm², 150mm², 185mm², 240mm², 300mm², 400mm², 500mm², 630mm², 800mm² |
| Insulation Material | XLPE (Cross-linked Polyethylene) |
| Insulation Thickness | 0.7mm – 2.0mm (depending on conductor size, per IEC 60502-1) |
| Sheath Material | PVC (Polyvinyl Chloride) – Type ST2 |
| Sheath Color | Black (standard), custom colors available |
| Operating Temperature (Normal) | -15°C to +90°C |
| Operating Temperature (Emergency Overload) | +130°C (max) |
| Short Circuit Temperature | +250°C (max, ≤5 seconds) |
| Minimum Installation Temperature | 0°C (cable should be preheated if below 0°C) |
| Minimum Bending Radius (Single Core) | 20 × overall diameter (unarmoured) |
| Flame Retardant | Optional (IEC 60332-1 or GB/T 18380) |
| UV Resistance | Yes (UV stabilized PVC sheath) |
Available Sizes & Current Ratings (Single Core, 90°C XLPE, in Air)
*Typical values – based on IEC 60502-1 and industry standards *
| Conductor Size (mm²) | Insulation Thickness (mm) | Sheath Thickness (mm) | Approx. Overall Diameter (mm) | Approx. Weight (kg/km) | Current Rating (Air, 90°C) |
|---|---|---|---|---|---|
| 1 × 16mm² | 0.7 | 1.5 | ~9 | ~120 | ~80A |
| 1 × 25mm² | 0.9 | 1.5 | ~10 | ~170 | ~105A |
| 1 × 35mm² | 0.9 | 1.5 | ~11 | ~220 | ~130A |
| 1 × 50mm² | 1.0 | 1.5 | ~13 | ~290 | ~160A |
| 1 × 70mm² | 1.1 | 1.5 | ~15 | ~390 | ~200A |
| 1 × 95mm² | 1.1 | 1.5 | ~17 | ~510 | ~245A |
| 1 × 120mm² | 1.2 | 1.5 | ~19 | ~630 | ~285A |
| 1 × 150mm² | 1.4 | 1.6 | ~22 | ~770 | ~330A |
| 1 × 185mm² | 1.6 | 1.6 | ~24 | ~940 | ~380A |
| 1 × 240mm² | 1.7 | 1.7 | ~28 | ~1200 | ~450A |
| 1 × 300mm² | 1.8 | 1.8 | ~31 | ~1480 | ~520A |
Values are indicative for single core unarmoured cable. Current ratings depend on installation conditions (ambient temperature, grouping, soil thermal resistivity). Please request official datasheet for exact specifications.
NA2XY vs YJLV – Naming Convention
| Designation | Standard | Region | Meaning |
|---|---|---|---|
| NA2XY | European / IEC | International | N = Standard (VDE) / A = Aluminum conductor / 2X = XLPE insulation / Y = PVC sheath |
| YJLV | Chinese / GB | China | YJ = XLPE insulation / L = Aluminum conductor / V = PVC sheath |
*Both designations refer to the same cable construction: Aluminum conductor, XLPE insulation, PVC sheath, rated 0.6/1kV .*
Why Choose Aluminum (NA2XY/YJLV) Over Copper?
| Feature | Aluminum (NA2XY/YJLV) | Copper |
|---|---|---|
| Weight | ~50% lighter | Heavier |
| Material Cost | 40-60% lower | Higher |
| Conductivity (% IACS) | ~61% | 100% |
| Required size for same ampacity | Approximately 1.5-2 sizes larger | Smaller |
| Corrosion resistance | Good (native oxide layer) | Very good |
| Termination | Requires aluminum-rated lugs | Standard lugs work |
| Flexibility | Good (Class 2 stranded) | Excellent |
Key consideration: When replacing a copper cable with an aluminum cable for the same ampacity, select one to two sizes larger (e.g., 50mm² copper → 70mm² or 95mm² aluminum).
Why Choose XLPE Insulation Over PVC?
| Feature | XLPE (Cross-linked Polyethylene) | PVC (Polyvinyl Chloride) |
|---|---|---|
| Continuous operating temperature | 90°C | 70°C |
| Emergency overload temperature | 130°C | 100°C |
| Short circuit temperature | 250°C | 160°C |
| Current carrying capacity | Higher (due to higher temperature rating) | Lower |
| Dielectric strength | Excellent | Good |
| Moisture resistance | Excellent | Good |
| Environmental impact | Lower (no halogens in insulation) | Higher (contains chlorine) |
Standards Compliance
| Standard | Description |
|---|---|
| IEC 60502-1 | Power cables with extruded insulation for rated voltages 1kV and 3kV |
| IEC 60228 | Conductors of insulated cables |
| GB/T 12706.1 | Chinese national standard equivalent to IEC 60502-1 |
| IEC 60332-1 | Tests on electric cables under fire conditions (flame retardant – optional) |
Installation Guidelines
Preparation
Inspect the cable for any damage to the PVC sheath before installation
Store cables on clean, dry reels, protected from direct sunlight and moisture
Preheat the cable if ambient temperature is below 0°C – cold cable can crack the PVC sheath
Pulling and Bending
| Parameter | Value |
|---|---|
| Minimum bending radius (single core, unarmoured) | 20 × overall diameter |
| Maximum pulling tension | Approximately 15 × conductor cross-section (mm²) in Newtons |
| Sidewall pressure limit | Consult engineering datasheet for specific values |
Termination
Use connectors rated for aluminum – standard copper lugs can cause galvanic corrosion and loose connections
Apply anti-oxidant compound to conductor surfaces before termination
Use torque wrench to ensure proper tightening – aluminum requires more precise torque than copper
Testing After Installation
Perform high voltage test at 3.5kV DC for 15 minutes (per IEC 60502-1)
Check continuity of all conductors
Verify insulation resistance (minimum 100 MΩ)
Comparison with Other Aluminum Cables
| Feature | NA2XY / YJLV | NAYY / YJV | YJLV32 / NA2XY with SWA |
|---|---|---|---|
| Conductor | Aluminum | Aluminum | Aluminum |
| Insulation | XLPE | PVC | XLPE |
| Sheath | PVC | PVC | PVC |
| Armour | None | None | Steel wire armour (SWA) |
| Temperature rating | 90°C | 70°C | 90°C |
| Mechanical protection | Low | Low | High |
| Direct burial suitability | Limited (use caution) | Limited | Yes |
| Cost | Moderate (XLPE cost premium) | Low | Higher (due to armour) |
| Typical application | Indoor, tray, conduit | General purpose | Underground, harsh environments |
Frequently Asked Questions (FAQ)
Q: What does NA2XY mean?
A: NA2XY is the European designation: N = Standard (VDE), A = Aluminum conductor, 2X = XLPE insulation, Y = PVC sheath .
Q: What does YJLV mean?
A: YJLV is the Chinese designation: YJ = XLPE insulation, L = Aluminum conductor, V = PVC sheath .
Q: Are NA2XY and YJLV the same cable?
A: Yes. They refer to the same construction: aluminum conductor, XLPE insulation, PVC sheath, rated 0.6/1kV. NA2XY is the European naming convention, YJLV is the Chinese naming convention .
Q: What is the temperature rating of the XLPE insulation?
A: XLPE insulation is rated for 90°C continuous operation, 130°C emergency overload, and 250°C short circuit (≤5 seconds) .
Q: Can this cable be used outdoors?
A: Yes. The PVC sheath is UV stabilized for outdoor exposure. However, for direct burial in areas with rodent risk, consider an armoured version (YJLV32 / NA2XY with SWA) .
Q: Is this cable flame retardant?
A: Standard NA2XY/YJLV is not flame retardant. Flame retardant versions are available upon request, complying with IEC 60332-1 or GB/T 18380-3 .
Q: Do you provide free samples?
A: Yes, we provide free samples of NA2XY/YJLV cable. The customer is only responsible for the shipping cost.
Q: Can you provide MTC and COC for this cable?
A: Yes, we provide Mill Test Certificates (MTC) and Certificates of Conformance (COC) with every shipment. Sample documents can be provided for your technical team to review.
Q: What is the minimum order quantity (MOQ)?
A: MOQ depends on the conductor size. For standard sizes (16mm² to 240mm²), we accept orders as low as 500 meters for trial purposes.
Q: What connectors should I use for aluminum cable termination?
A: Always use connectors specifically rated for aluminum (typically tin-plated or bi-metallic lugs). Apply anti-oxidant compound and use a torque wrench for proper tightening.
Q: What is the typical lead time?
A: Typical lead time is 15–25 days after deposit confirmation, depending on order quantity and conductor size.
Q: Can I get custom printing on the cable?
A: Yes, we support OEM/ODM orders including custom printing (project name, customer logo, sequential metering, voltage marking).
![]()
![]()
![]()
![]()
![]()