logo

64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable

기본 특성
원산지: 헤베이, 중국
브랜드 이름: HV High Voltage Power Cable
인증: CCC,IEC,VDE,TUV,ISO
모델 번호: 비커스경도 케이블
부동산 거래
최소 주문 수량: 협상 가능
가격: 협상 가능
지불 조건: l/c, t/t
공급능력: 주 500km
명세서
Insulation Material: XLPE Jacket: 체육
Conductor Material: 가닥 원형 또는 세그먼트 (Milliken) 압축 구리 도체 Nominal Voltage: 38/66kV (72.5kV)
Core: 1 핵심 Application: 지하철
High Light:

110kV high voltage power cable

,

XLPE insulated power cable

,

300-2500mm high voltage cable

제품 설명

64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable


APPLICATION

The cable is suitable for use in high voltage transmission networks, in systems of rated voltages from 110 kV grade up to and including 115 kV grade.


CONSTRUCTION

  64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable 064/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable 1


  • Conductor: Stranded circular or segmental (Milliken) compacted copper conductor 
  • Conductor shield:Semi-conductive shield 
  • Insulation: Cross-Linked Polyethylene(XLPE) 
  • Insulation shield: Semi-conductive shield 
  • Metal shielding layer:Corrugated Aluminum Sheath or Lead Sheath or Aluminum Laminated Tape
  • Binder tape:Non-woven fabrics 
  • Metal Laminate Foil: Aluminum laminated tape
  • Outer sheath: PE


STANDARD 


IEC 60840 IEC 62067


CHARACTERISTIC 


  • Voltage Rating Uo/U: 64/110kV(123kV) 
  • ‌Continuous Operation: ‌+90°C‌ Conductor Temp 
  • ‌Emergency Overload‌:‌+105°C‌ Conductor Temp (≤100 hrs/year, ≤500 hrs/lifetime)
  • Short Circuit:‌‌+250°C‌ Conductor Temp (for calculated duration, typically 1-5s) 
  • ‌Installation‌≥ 0°C
  • ‌Ambient Operation ‌≥ -40°C


PARAMETERS


Conductor

Insulation

Nominal Area of Copper Wires

Outer Jacket

Nominal
  Area

Max.DC
resistance at 20

Max.AC
resistance at 90

Nominal Thickness of Insulation
          Layers

Nominal
Thickness

Approx.
Overall
Diameter

Approx.
Overall
Weight

Cond.
Screen

XLPE

Ins.
Screen

mm²

Ω/km

Ω/km

mm

mm

mm

mm²

mm

mm

kg/m

300 R

0.0601

0.0787

1.2

15

1

95

3.5

67.9

6.47

400 R

0.047

0.0627

1.2

15

1

95

3.5

70.5

7.41

500 R

0.0366

0.0502

1.2

15

1

95

4

74.9

8.79

630 R

0.0283

0.0407

1.2

15

1

95

4

78.4

10.21

800 R

0.0221

0.0338

1.2

15

1

95

4

82.4

12.17

1000 S

0.0176

0.024

1.5

15

1.2

95

4

92.1

14.74

1200 S

0.0151

0.0211

1.5

15

1.2

95

4.5

97.1

17

1400 S

0.0129

0.0185

1.5

15

1.2

95

4.5

99.1

18.99

1600 S

0.0113

0.0168

1.5

15

1.2

95

4.5

103.1

20.72

2000 S

0.009

0.0143

1.5

15

1.2

95

4.5

108.1

24.42

2500 S

0.0072

0.0125

1.5

15

1.2

95

4.5

116.1

29.99


OUR FACTORY


64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable 2


PROJECT

64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable 3



APPLICATION


64/110kv HV High Voltage Power Cable CU/XLPE/CWS/STA 123kV 300-2500mm Power Cable 4



FAQ

1.What are the typical applications for 64/110kV cables?

  • Substation interconnections (GIS to transformer bays)
  • Underground transmission networks in urban areas
  • Power distribution for industrial complexes requiring high-voltage input

2.How does corrugated steel sheath (CWS) enhance cable performance?

  • Provides mechanical protection against rodent damage
  • Improves water resistance in underground or submarine installations
  • Maintains structural integrity under thermal expansion (operating temp: -25°C to +90°C)

3. What bending radius should be maintained during installation?

  • Minimum bending radius: 20 times outer diameter (for single-core cables)
  • For 2500mm² cable (OD≈120mm): ≥2.4m to avoid conductor deformation

4. How are 64/110kV cables terminated?

  • GIS terminals (gas-insulated switchgear) for substations
  • Outdoor porcelain or composite terminals with stress cones
  • Prefabricated joints for field splicing (waterproof design)

5.How does XLPE insulation compare to oil-paper insulation?

  • Higher dielectric strength (≥200kV/mm vs 150kV/mm)
  • No oil maintenance required
  • Lighter weight (30% reduction for same voltage rating)

6. What are the storage requirements for 64/110kV cables?

  • Reels stored upright with anti-roll blocks
  • Temperature: -15°C to +40°C
  • Shelf life: ≤12 months (UV-protected wrapping needed for outdoor storage)

7.How to calculate the ampacity of 2500mm² 64/110kV cable?

  • In air: ≈1200A (ambient 30°C, soil thermal resistivity 1.2K·m/W)
  • In duct: ≈800A (grouped with 3 other cables)
  • Reference: IEC 60287-1-1 with derating for CWS sheath